DC Voltage Measurement
|
Range
|
Resolution
|
Accuracy
|
Input Impedance
|
Overload Protection
|
0.1V to 600V
|
0.1V
|
±(0.5% of rdg + 1dgt)
|
3MΩ
|
605V AC max RMS
|
|
|
AC Voltage Measurement
|
Range
|
Resolution
|
Accuracy
|
Input Impedance
|
Overload Protection
|
0.1V to 600V
|
0.1V
|
±(0.8% of rdg + 4dgt)
|
3MΩ
|
605V AC max RMS
|
|
Max crest factor
|
|
Resistance Measurement/Test Continuity with buzzer
|
Range
|
Resolution
|
Accuracy
|
Overload Protection
|
0.1Ω to 199.9Ω
|
0.1Ω
|
±(2.0% of rdg + 3dgt)
|
605V AC max RMS
|
|
The buzzer sounds when measured resistance is lower than 30 ohms.
|
|
LO Ohms
|
Range
|
Resolution
|
Accuracy
|
Overload Protection
|
0.01Ω to 19.99Ω
|
0.01Ω
|
±(2.0% of rdg + 3dgt)
|
605V AC max RMS
|
|
Test Current:
|
>200mA DC up to 5 ohms (including cable resistance).
|
Test Current:
|
>45mA DC up to 5 ohms (including cable resistance).
|
Open Circuit Voltage: 4V <VO <24V
|
|
|
MOhm: Insulation Resistance (Auto Ranging)
|
Test Voltage
|
Resistance Range
|
Resolution
|
Accuracy
|
Overload Protection
|
250V
|
0.001 to 0.100MΩ
|
0.001MΩ
|
±10 digits
|
605V max RMS
|
0.101 to 3.999MΩ
|
0.001MΩ
|
±(2.0% rdg + 5 dgt)
|
4.00 to 39.99MΩ
|
0.01MΩ
|
40.0 to 399.9MΩ
|
0.1MΩ
|
±(5.0% rdg + 5 dgt)
|
400 to 1000MΩ
|
1MΩ
|
500V
|
0.001 to 0.250MΩ
|
0.001MΩ
|
±15 digits
|
0.251 to 3.999MΩ
|
0.001MΩ
|
±(2.0% rdg + 5 dgt)
|
4.00 to 39.99MΩ
|
0.01MΩ
|
40.0 to 399.9MΩ
|
0.1MΩ
|
400 to 2000MΩ
|
1MΩ
|
±(5.0% rdg + 5 dgt)
|
1000V
|
0.001 to 0.250MΩ
|
0.001MΩ
|
±15 digits
|
0.251 to 3.999MΩ
|
0.001MΩ
|
±(2.0% rdg + 5 dgt)
|
4.00 to 39.99MΩ
|
0.01MΩ
|
40.0 to 399.9MΩ
|
0.1MΩ
|
400 to 1000MΩ
|
1MΩ
|
±(3.0% rdg + 5 dgt)
|
1000 to 4000MΩ
|
1MΩ
|
±(5.0% rdg + 10 dgt)
|
|